Industries / Industrial equipment and services / IoT and industrial automation
Control rooms
A control room is where operators watch and run a plant through screens, and its design decides what they can see and how fast they can act.
6
Milestones achieved, from 1975 to 2023.
2
To watch for: announced, not yet confirmed outside.
2
Open deliverables. Nobody has shipped them.
The road
AchievedWatch forOpen
Achieved
1975
Screens replace panel walls
Honeywell's TDC 2000 and Yokogawa's CENTUM spread control over many microprocessor units and gave operators screens in place of walls of panel instruments. ISA's magazine calls the TDC 2000 "the beginning of commercial DCSs" (distributed control systems) and says Yokogawa introduced CENTUM "about the same time"; each company calls its own system the world's first, and Honeywell notes that other companies released such systems in 1975 as well.
Credit
Honeywell; Yokogawa
1979
A control room fails
At Three Mile Island Unit 2 in Pennsylvania a relief valve stuck open for 2 hours and 22 minutes, while a panel light that showed only that power to the valve had gone off led operators to believe it had shut. The President's Commission found a panel with hundreds of alarms, key indicators placed where operators could not see them, one light covered by a maintenance tag, and more than 100 alarms in the first few minutes with no way to suppress the unimportant ones.
LessonThe commission found the control room might be adequate for normal running but "seriously deficient under accident conditions.".
Credit
President's Commission on the Accident at Three Mile Island, chaired by John G. Kemeny
1994
Upsets become a research field
In November 1994 a research joint venture led by Honeywell, with members including Amoco, BP, Chevron, Exxon, Mobil, Shell and Texaco and matching money from the US National Institute of Standards and Technology, began studying how operators cope with abnormal situations. Honeywell put the cost of preventable losses from such situations at "at least $20B annually" to the US economy. The Abnormal Situation Management (ASM) Consortium went on to publish guidelines for alarm management and console screen design.
Credit
Honeywell and the ASM Consortium members
2010
Mines run from far away
On 25 June 2010 Rio Tinto opened a $60 million operations centre in Perth from which controllers and schedulers run iron ore mines, railways and ports in Western Australia's Pilbara, up to 1,500 km away, IBTimes and the Australian Associated Press reported. Rio Tinto's Sam Walsh said: "No one else in the mining industry is doing this."
Credit
Rio Tinto
2015
A standard for operator screens
Operator screens are known in the trade as HMIs (human-machine interfaces). In 2008 Bill Hollifield, Dana Oliver, Ian Nimmo and Eddie Habibi published The High Performance HMI Handbook, and in July 2015 ISA released ISA-101.01-2015, a standard that covers "the philosophy, design, implementation, operation, and maintenance of HMIs for process automation systems." IEC approved it in early 2020 for adoption as IEC 63303.
Credit
Bill Hollifield, Dana Oliver, Ian Nimmo and Eddie Habibi; the ISA101 committee
2023
AI runs a distillation column
After a 35-day field test from 17 January to 21 February 2022, ENEOS Materials formally adopted Yokogawa's reinforcement-learning controller, FKDPP, to run a distillation column. Reinforcement learning trains software by trial and error. Yokogawa reports that steam use, and the carbon dioxide that goes with it, fell 40% against the previous manual control, and said in November 2026 that the plant had run stably for more than four years.
Credit
Yokogawa and ENEOS Materials
Watch for
Agents in the control room
Honeywell says its Experion Cognition software makes "recommendations and automated decisions," with agents that "proactively act on behalf of the operator," tested in a live proof of concept at Borouge International's site in Ruwais, United Arab Emirates. It says its software predicted alarm incidents an average of 5 to 10 minutes before they happened across pilots, without saying how many.
Achieved whenBorouge, another operator or an outside party publishes measured results from routine use, including how often the predictions were wrong.
Claimed by
Honeywell, June 2026
AI control inside the DCS
Yokogawa says version R7.02 of its CENTUM control system, released on 19 November 2026, runs AI control models as a standard function, a step "from automation to autonomy."
Achieved whencustomers other than ENEOS Materials report routine closed-loop use on CENTUM.
Claimed by
Yokogawa, November 2026
Open
01
An operator screen checker
A program that takes screenshots of operator screens and checks each against published high-performance HMI practice, such as grey backgrounds, colour kept for abnormal states and navigation in the same place on every screen, and lists each breach with where it appears.
The briefCredit · unclaimed02
An AI helper under test
A study that puts a working AI assistant, a language model reading the alarm list and trends of a simulated plant, beside experienced console operators during alarm floods, and measures how fast and how accurately they find the cause with and without it, including runs where the assistant is wrong.
The briefCredit · unclaimed
Open 01 · the brief
An operator screen checker
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A program that takes screenshots of operator screens and checks each against published high-performance HMI practice, such as grey backgrounds, colour kept for abnormal states and navigation in the same place on every screen, and lists each breach with where it appears.
Why it is still open
Screen reviews are done by people: a May 2026 guide to ISA-101 design describes a manual "squint test," and ISA's 2019 technical report on HMI usability treats audit and validation as continuing work processes. Searches found no tool, dataset or study that scores operator screens automatically.
Built with what exists
AI models that read screenshots, such as Claude or Gemini; FUXA, an open-source web-based HMI and SCADA program (MIT licence), to build test screens; a rule list written in the builder's own words from public guidance.
First step
Write 15 checks from public high-performance HMI guidance, build 20 test screens in FUXA with known breaches, and score one model on them.
Done looks like
On 200 screenshots from at least three makers' systems, the checker's findings agree with those of two experienced HMI designers on at least 90% of checks, with the screenshots, rules and scores published.
Open 02 · the brief
An AI helper under test
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A study that puts a working AI assistant, a language model reading the alarm list and trends of a simulated plant, beside experienced console operators during alarm floods, and measures how fast and how accurately they find the cause with and without it, including runs where the assistant is wrong.
Why it is still open
The closest study, a 2025 Polytechnique Montréal thesis by Karine Ung, had researchers play the part of the tool for 20 chemical-engineering students; the tool helped when it was right, and students kept following its wrong diagnoses. Makers' new alarm agents, such as Emerson's for its Ovation control system, come without published measurements.
Built with what exists
PER4Mance, the thesis's open-source simulator and operator screen for the Tennessee Eastman process, a standard test chemical plant (MIT licence, built in MATLAB and Simulink); a language model with read-only access to the alarm and trend data.
First step
Install PER4Mance from GitHub, run its loss-of-feed fault, and log what a language model names as the cause from the alarm list alone.
Done looks like
At least 12 operators with at least three years at a console, each handling at least ten flood scenarios, with time to diagnosis and accuracy published for three conditions: no assistant, a correct assistant and one that is wrong in a quarter of runs.