Industries / Construction and property / Fire protection and life safety
Special hazard systems
Special hazard work protects places where water would fail or do harm, such as computer rooms, fuel stores, aircraft hangars, ships' engine rooms and restaurant kitchens, with fixed systems that release gas, foam, wet chemical or fine water mist.
7
Milestones achieved, from 1966 to 2025.
2
To watch for: announced, not yet confirmed outside.
2
Open deliverables. Nobody has shipped them.
The road
AchievedWatch forOpen
Achieved
1966
Foam that films over fuel
On 28 June 1966 the US Navy received a patent, filed in 1963 by Richard L. Tuve and Edwin J. Jablonski, for putting out burning liquid fuel with a water-based foam holding about 0.1 to 10% by weight of a fluorocarbon surfactant, a soap-like chemical built on carbon-fluorine bonds. The patent says a thin film spreads over the fuel under the foam and quickly re-forms when broken. Foams with fluorinated chemicals of this family, called PFAS, are still relied on in fixed systems: the European Union's 2025 restriction (below) gives its longest grace period, to 2035, to major chemical and fuel sites, offshore oil and gas installations and naval ships.
LessonA foam chosen for how well it worked on fuel later had to be replaced for what it does in the environment, and fixed systems built around it must be cleaned and refitted.
Credit
Richard L. Tuve and Edwin J. Jablonski, for the US Navy
1994
Halon production ends
Halon 1301 is a gas that stops fire by interrupting the chemical reactions of burning, without leaving residue, and it was used from the 1960s to protect aircraft, computer centers, energy plants and military equipment. It also destroys ozone, and under the Montreal Protocol US production and import of new halons ended on 1 January 1994. Since then only recycled halon has been sold, and the US Environmental Protection Agency (EPA) says it is still used in civil aircraft, older military systems and oil and gas exploration. In July 2025 Tradewater, a carbon credit developer, exported 30,000 lb (about 13,600 kg) of Halon 1301 to France to be destroyed for carbon credits, by EPA's account; EPA says it stopped the destruction because the gas could be reclaimed, and in September 2025 it ordered Tradewater, Wesco and the American Carbon Registry (ACR) to report on their halon projects. On 31 March 2026 ACR changed its rules so that only Halon 1301 less than 99.6% pure can earn credits.
LessonOnce production stops, the remaining stock is all there is, and a market that pays to destroy it can drain what aircraft still need.
epa.govepa.govepa.govacrcarbon.orginternationalfireandsafetyjournal.com
Credit
the parties to the Montreal Protocol; US EPA; ACR
1994
A harder kitchen test
UL 300, Underwriters Laboratories' fire test for the fixed systems that protect restaurant cooking appliances and the hoods and ducts above them, took effect in a stricter form on 21 November 1994. The tests moved to real commercial fryers kept burning with the fuel on, a two-minute pre-burn in place of one minute, and vegetable shortening that ignites at 685 °F (363 °C) or higher, in place of animal fat. The fire department of Lafayette, Indiana, says low-fat oils and well-insulated fryers had made most dry chemical agents ineffective, and the Fire Equipment Manufacturers' Association says fryers now need on average five times more wet chemical agent to pass.
LessonA change in what kitchens cooked with outran systems that had been tested on older fats.
Credit
Underwriters Laboratories
2000
Carbon dioxide's death toll
Carbon dioxide puts out fires by pushing oxygen out of a room, at concentrations that also kill people. As users looked for halon replacements, the US EPA published a review in 2000 that found 51 incident records from 1975 on, reporting 72 deaths and 145 injuries from discharges of carbon dioxide fire systems. All the deaths were by asphyxiation, and most incidents happened during maintenance on or near the system, often when someone set it off by accident. The review notes that the 2000 edition of NFPA 12, the US standard for carbon dioxide systems, was to require the protected space to be evacuated before testing or maintenance.
LessonAn agent that spares the equipment can still leave no air for people, so the rules for locking a system out before work matter as much as the system.
Credit
US Environmental Protection Agency
2016
A gas test breaks drives
On 10 September 2016 a planned test of the inert gas fire system in ING Bank's main data center in Bucharest, Romania, damaged dozens of hard drives, and cash machines, card payments and online banking were down for about 10 hours until work moved to a backup site, Data Center Dynamics reported. The gas, Inergen, does not harm electronics; the vibration from the noise of its release did. A source told Motherboard the noise was over 130 dB, and Siemens had concluded in a white paper that drive faults after such discharges are caused by noise. A 2022 laboratory study by Marco Strianese and colleagues found that silent nozzles kept the noise generally below a 110 dB threshold, but that high-pitched sound could still slow drives below it.
LessonA system can work exactly as designed and still damage what it was installed to protect.
Credit
ING Bank (operator); Siemens; Strianese and colleagues
2022
The clean agent maker exits
Clean agents are gases or fast-evaporating liquids that put out fires and leave no residue. On 20 December 2022 3M said it would stop making PFAS, including its fluorinated fluids, by the end of 2025. Fike, a maker of suppression systems, said this would end 3M's Novec 1230, a popular clean agent, and now sells SF 1230, which it says is the same compound, FK-5-1-12. Fike also notes that hydrofluorocarbons (HFCs), the family that includes the clean agent FM-200, are being phased down through 2036 under the American Innovation and Manufacturing (AIM) Act, a US law enacted on 27 December 2020.
LessonEach of halon's replacements has fallen under a later environmental rule, first on climate and then on PFAS, so an agent can become hard to buy within a system's working life.
Credit
3M; Fike; US EPA
2025
Europe restricts PFAS foam
On 2 October 2025 the European Commission amended REACH, the EU's chemicals law, to restrict PFAS in firefighting foams. From 23 October 2030, foams holding 1 mg/L or more of all PFAS combined may not be sold or used. The sale of such foam in portable extinguishers ends sooner, and the longest grace period, to 23 October 2035, goes to sites covered by the Seveso Directive on major chemical hazards, offshore oil and gas installations, naval ships and some civilian ships. Equipment cleaned and refilled with fluorine-free foam may carry up to 50 mg/L of leftover PFAS. Replacements are reaching fixed systems: in March 2026 Perimeter Solutions said FM had approved its SOLBERG EVOLUTION 3% fluorine-free foam to standard FM 5130 for fixed sprinkler systems in places such as aircraft hangars and fuel stores, used with the company's own tanks and system hardware.
Credit
European Commission; FM Approvals
Watch for
Water mist replacing sprinklers
Water mist systems spray a much finer mist than sprinklers and use less water. iCO, a UK maker, says its concealed low-pressure water mist nozzle passed fire testing to BS EN 14972-17, the European test for water mist in homes, and that systems using it may serve in place of sprinklers in residential buildings up to 45 m tall, with nozzles no higher than 3.5 m and up to 50% less stored water. How water mist performs in real fires is unsettled: a report by Optimal Economics for the British Automatic Fire Sprinkler Association, published in March 2026, found that England's fire incident records, which held 2,924 fires with sprinklers or water mist present from 2018/19 to 2023/24, cannot be used to compare the two.
Achieved whena third-party certification body lists the nozzle, and outside fire records show how such systems perform in homes.
internationalfireandsafetyjournal.cominternationalfireandsafetyjournal.com
Claimed by
iCO, October 2026
Fluorine-free foam on ships
Survitec, which makes marine fire systems, says it has tested alcohol-resistant fluorine-free foam concentrates, which are thicker than the foams ship systems were built for, and found that changes to existing proportioners, the devices that mix concentrate into water, keep the mix within the marine rule of 0% to +30% of the set ratio without replacing whole systems. It tied the work to the International Maritime Organization's ban on PFOS foams, which it says applies from January 2026.
Achieved whena classification society or flag state publishes approval of the modified systems, or an outside test confirms the dosing accuracy.
Claimed by
Survitec, June 2025
Open
01
A register of fluorine-free foams
A public table of fluorine-free foam concentrates sold for fixed systems, giving for each the approvals it actually holds (UL 162 listing, FM 5130 approval, EN 1568 class, LASTFIRE result, ICAO level, the US Department of Defense's qualified products list), the fuels, application rates and hardware each approval covers, and a link to the certifier's own record for every entry.
The briefCredit · unclaimed02
Count halon destroyed for credits
A public ledger of every project that has destroyed halon for carbon credits since the first in 2022, giving the registry, project ID, developer, source of the halon, mass destroyed, purity and credits issued, with a link for each figure, and a comparison of the total with published estimates of the halon still held for aircraft and other users.
The briefCredit · unclaimed
Open 01 · the brief
A register of fluorine-free foams
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A public table of fluorine-free foam concentrates sold for fixed systems, giving for each the approvals it actually holds (UL 162 listing, FM 5130 approval, EN 1568 class, LASTFIRE result, ICAO level, the US Department of Defense's qualified products list), the fuels, application rates and hardware each approval covers, and a link to the certifier's own record for every entry.
Why it is still open
Under the EU's 2025 restriction, owners of most fixed foam systems in Europe must change to fluorine-free foam by October 2030, and major chemical sites by October 2035. The approvals they need to compare are scattered. UL's Product iQ covers only UL listings; makers' catalogs, such as Perimeter Solutions', filter only their own products by approval; FM approvals are tied to particular hardware, as Perimeter's is to its own tanks, foam chambers and sprinkler heads; and an August 2026 article sponsored by a foam maker warns that "tested to UL-162 protocols" is not the same as being UL-listed. Two narrower lists exist: the US Department of Defense's qualified products list for its own fluorine-free specification, and Clean Production Action's GreenScreen certification of PFAS-free foams, which in May 2022 covered 15 products from five makers and records no fire approvals. Searches found no register across all of them.
lawplayer.comperimeter-solutions.cominternationalfireandsafetyjournal.comfireengineering.comcleanproduction.org
Built with what exists
UL Product iQ; FM Approvals' online Approval Guide; the Department of Defense's qualified products list; makers' data sheets; a low-cost AI model to pull the claims out of each data sheet (see the Note "The jobs agents repeat"); an agent that keeps the link behind each finding (see the Note "Findings that cite notes").
First step
List the fluorine-free foams in Perimeter Solutions' public catalog, note the approvals each data sheet claims, and check the FM claims against FM's Approval Guide.
Done looks like
At least 50 concentrates from at least 10 makers, each claimed approval marked confirmed, not found or contradicted by the certifier's record, with a second person rechecking a random 10% of rows.
Open 02 · the brief
Count halon destroyed for credits
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A public ledger of every project that has destroyed halon for carbon credits since the first in 2022, giving the registry, project ID, developer, source of the halon, mass destroyed, purity and credits issued, with a link for each figure, and a comparison of the total with published estimates of the halon still held for aircraft and other users.
Why it is still open
Tradewater announced the first such project in February 2022, destroying about 2,687 lb (about 1,219 kg) of Halon 1301 under ACR's method. In September 2025 EPA ordered Tradewater, Wesco and ACR to say how many halon projects they had submitted and how many credits each earned, but their answers have not been published, and ACR's March 2026 rule change limits only future projects. Searches found no public total.
Built with what exists
ACR's public registry reports and those of other carbon registries; the Berkeley Carbon Trading Project's Voluntary Registry Offsets Database, a free spreadsheet (CC BY 4.0 license) of all projects and credit issuances on six registries, ACR among them; a browser agent to page through them slowly and within each site's rules (see the Note "Deleting 80% to start over"); an agent that keeps the source of each number (see the Note "Findings that cite notes"); halon reports of the UN Environment Programme's Halons Technical Options Committee for the estimates of remaining stock.
First step
Find Tradewater's 2022 halon project in ACR's public registry reports and record its mass, purity and credits.
Done looks like
Every halon destruction project on ACR's registry from 2022 to 2026 listed with mass and credits, a total in kilograms and in credits with each figure linked, all rows rechecked by a second person, and the total set against at least one published estimate of the remaining stock.