This work fits instruments in the plant and runs the tubing, air lines, cable, earthing and heat tracing that connect them to the process and to the control system.

4

Milestones achieved, from 1947 to 1989.

0

To watch for: announced, not yet confirmed outside.

2

Open deliverables. Nobody has shipped them.

The road

AchievedWatch forOpen

Achieved

  1. 1947

    A fitting with two ferrules

    Instrument tubing is small stainless steel or copper tube that carries process pressure to an instrument or air to a valve. It is joined with compression fittings, in which a nut squeezes rings called ferrules onto the tube to grip and seal it. Swagelok's history says its two-ferrule fitting was developed after Fred A. Lennon met Cullen B. Crawford; the two formed the Crawford Fitting Company in July 1947, and the next year Lennon bought the whole business and the patent. The company says the fitting is made up by its geometry rather than by torque, so a correct joint can be checked with a gauge.

    swagelok.comnortherncal.swagelok.com

    Credit

    Cullen B. Crawford and Fred A. Lennon, Crawford Fitting Company (now Swagelok)

  2. 1972

    Heating cable cut to length

    Heat tracing is electric cable run along pipes and instrument lines to keep them from freezing or to hold them at a process temperature. Before 1972 it used mineral-insulated cable made to a set length in a factory, and because pipework as built never quite matched the drawings, cables often went back for a different length. In 1972 Raychem Corporation patented and began making a self-regulating cable: a polymer filled with carbon black, laid between two bus wires, conducts less as it warms, so each short stretch of cable controls its own heat and the cable can be cut to length on site. The IEEE, the professional body of electrical engineers, lists it as an IEEE Milestone and says most electric heat tracing is now self-regulating, made by more than ten companies.

    Lessona product that fits the plant as built does better than one that fits the drawing.

    ethw.org

    Credit

    Raychem Corporation

  3. 1989

    A grounding guide for signals

    Instrument signals are small currents and voltages, and stray currents in a plant's earthing system can appear in them as noise. IEEE 1050, the IEEE's guide to grounding instrumentation and control equipment in generating stations, published on 29 September 1989, set out how to protect people and equipment while giving signal references "suitable electric noise immunity", and it treated a station's connections to nearby substations as a large source of noise. It was replaced by a revised edition in 1996.

    standards.ieee.org

    Credit

    IEEE

  4. 1989

    Air hoses fitted backward

    On 23 October 1989 a vapor cloud exploded at Phillips 66's polyethylene plant in Pasadena, near Houston, killing 23 people. A ball valve meant to isolate a reactor's settling leg during maintenance was open: the air hoses to its actuator, the device that moves the valve, had been cross-connected, so the air that should have closed it opened it. Site rules said the hoses were to be disconnected before the work, and an IChemE summary lists among the root causes that the actuator had interchangeable hose connections.

    Lessonconnections that can be swapped will be swapped, so fittings should make a wrong connection impossible and a valve's movement should be checked after any reconnection.

    hse.gov.ukicheme.org

    Credit

    case records by the UK Health and Safety Executive (HSE) and the Institution of Chemical Engineers (IChemE)

Open

  1. 01

    Judge tube fittings by photo

    A phone app that photographs a made-up compression fitting and says whether the nut was tightened the right amount, by measuring the gap between nut and body against the maker's gauge value, and flags parts from different makers mixed in one joint.

    The brief
    Credit · unclaimed
  2. 02

    Shield faults from the signal

    A bench rig of 24 V, 4 to 20 mA instrument loops in which installation faults are planted one at a time (cable shield earthed at both ends with a small voltage between the two earths, a broken drain wire, a loose terminal, a damp junction box imitated with a resistor, interference coupled in from a coil driven by a signal generator), a public labeled set of loop-current recordings, and a model that names the fault from a recording.

    The brief
    Credit · unclaimed

Open 01 · the brief

Judge tube fittings by photo

Credit · unclaimed

The first to publish is credited on this line, and the deliverable moves from Open to Achieved.

What to build

A phone app that photographs a made-up compression fitting and says whether the nut was tightened the right amount, by measuring the gap between nut and body against the maker's gauge value, and flags parts from different makers mixed in one joint.

Why it is still open

The UK HSE's 2018 inspection guide for offshore plants expects procedures for "visual inspection of compression fittings for correct component selection and correct make-up (with use of manufacturer's gauge as applicable)", and asks operators to keep the number of fitting makes and types to a manageable level; the check is done by hand. A November 2026 search found camera systems that check brazed tube joints and bent tube shapes in factories, but no tool that judges a compression fitting's make-up from a photo.

hse.gov.ukroboflow.com

Built with what exists

a smartphone camera; open object detection and segmentation models that run on a phone, such as Ultralytics YOLO and Meta's Segment Anything; a printed scale target; a bench kit of unpressurized 1/4 in, 3/8 in and 1/2 in stainless fittings from two or three makers, with their gap inspection gauges.

  1. First step

    Make up 30 fittings of one size at five tightening levels, gauge each one, and photograph each from four angles.

  2. Done looks like

    On 300 fittings made up on a bench to known turns, some under-tightened, some correct and some over-tightened, photographed by three people on three phones, the app's pass or fail agrees with the gap gauge on at least 95% of them, with the photos and answer key published.

Open 02 · the brief

Shield faults from the signal

Credit · unclaimed

The first to publish is credited on this line, and the deliverable moves from Open to Achieved.

What to build

A bench rig of 24 V, 4 to 20 mA instrument loops in which installation faults are planted one at a time (cable shield earthed at both ends with a small voltage between the two earths, a broken drain wire, a loose terminal, a damp junction box imitated with a resistor, interference coupled in from a coil driven by a signal generator), a public labeled set of loop-current recordings, and a model that names the fault from a recording.

Why it is still open

Fluke's troubleshooting guide says poor or disconnected cable shields are frequent causes of noise that upsets readings and has technicians check shields and terminations by hand with meters and oscilloscopes, and published advice disagrees on whether to earth a shield at one end or both. Searches of the web, Zenodo and GitHub in November 2026 found no labeled recordings of loop faults; the nearest work is a 2019 GitHub project that uses graph analysis to locate ground loops in a laboratory.

fluke.comindustrialmonitordirect.com

Built with what exists

24 V DC supplies; two-wire transmitters or 4 to 20 mA loop simulators; shielded twisted-pair instrument cable; a USB data logger sampling at 10 kHz or more, such as a LabJack T7; a bench signal generator; Python with scikit-learn or PyTorch for the classifier.

  1. First step

    Build one loop with a transmitter simulator, a 250 ohm resistor and a data logger, and record ten minutes each with the shield earthed at one end, at both ends and not at all.

  2. Done looks like

    At least 1,000 labeled recordings covering eight fault types and a no-fault class on two cable lengths, released under an open license, and a model that names the fault correctly in at least 90% of recordings made on a second rig it was not trained on.