Industries / Industrial equipment and services / Industrial services / Instrumentation and electrical
Hazardous areas
This work installs, inspects and maintains electrical equipment in places where flammable gas, vapor or dust can be present, so that the equipment cannot set it alight.
5
Milestones achieved, from 1906 to 2010.
1
To watch for: announced, not yet confirmed outside.
2
Open deliverables. Nobody has shipped them.
The road
AchievedWatch forOpen
Achieved
1906
Narrow gaps stop flames
At the Gelsenkirchen-Bismarck test gallery in Germany's Ruhr coalfield, the mining official (Bergassessor) Beyling ignited firedamp, the methane and air mixture of coal mines, inside casings for electric motors and switchgear to see when the flame escaped. Casings fitted with wire gauze, the protection used in miners' safety lamps, had given poor results in tests in 1903. He found that thin gaps between metal faces, 0.5 mm wide and 50 mm long, let no explosion through, while a 1 mm gap did, so a strong casing need not be sealed with asbestos or rubber: the hot gases cool as they pass through the joint. A 35 horsepower motor failed the test because its stamped plates left gaps wider than 0.5 mm. This is the principle of the flameproof enclosure, called explosion-proof in North America.
Lessonthe gap is the protection, so it has to be made, and kept, to size.
Credit
Beyling, Gelsenkirchen-Bismarck test gallery; his report appeared in parts in the Annales des Mines de Belgique in 1906 and 1907
1931
Classes for hazardous locations
The US National Electrical Code (NEC), the wiring rulebook published by the National Fire Protection Association (NFPA), covered wiring in "extra-hazardous" locations from its 1920 edition. The 1931 edition added the term classification and Classes I, II and III for different kinds of hazard, and the 1947 edition split each location into Division 1 and Division 2, so the strictest rules apply where the hazard is greatest.
Credit
NFPA's National Electrical Code committees
1996
Zones enter the US code
Most of the world grades hazardous areas in zones (Zone 0, 1 and 2, from gas present continuously to gas present only rarely and briefly). The 1996 NEC added them in a new Article 505, after the NFPA Standards Council upheld a floor vote at a hearing on 19 July 1995. Don Zipse and Craig Wellman argued for the change on the grounds of international experience and trade; speakers for the electricians' union IBEW, the makers' association NEMA and the maker Crouse-Hinds argued it would confuse installers. The idea had first been proposed in 1969 for the 1971 code. The 1999 edition gathered the zone rules into Article 505.
LessonUS plants now use two systems side by side, so installers and inspectors have to know which one a drawing uses.
Credit
NFPA Standards Council; Don Zipse and Craig Wellman
2007
A tank gauge float sparks
On 17 July 2007 explosions and fire at the Barton Solvents facility in Valley Center, Kansas, led to the evacuation of thousands of residents. The CSB found that the float of the tank's level gauge had a loose linkage where it joined the gauge tape, which could separate slightly, break the float's path to ground and make a spark. Static charge built up while a nonconductive solvent, VM&P naphtha, was pumped in, and the CSB concluded the loose linkage was the most likely spark location; it estimated the vapor's minimum ignition energy at 0.22 millijoules. It recommended modifying or replacing loose-linkage level floats.
Lessonan instrument inside a tank can itself be the ignition source.
Credit
investigated by the CSB
2010
Ex workers certified by skill
The IECEx System, run by the International Electrotechnical Commission (IEC) to certify equipment for explosive atmospheres, has also certified people since late 2010. Its Certificate of Personnel Competence (CoPC) is issued by approved certification bodies after an assessment of the person, unit by unit: Ex 000 for entering a site with hazardous areas, Ex 002 for classifying areas, Ex 003 for installing, Ex 004 for maintaining, Ex 006 for testing and Ex 007 for visual and close inspection, among others. The rules, IECEx 05, reached edition 5.1 in September 2025.
Credit
the IEC's IECEx System
Watch for
AI reads Ex equipment
Mantl-Ex says its Mantl-Core software, through a phone app called Inspector Buddy, reads Ex ratings, temperature classes and protection types from photos and video of equipment, flags faults against hazardous area standards, and cuts a visual inspection from about 30 minutes to about 5 minutes per item. It says the system covers about 95% of a visual inspection, 75% of a close inspection and 50% of a detailed one, which needs the equipment opened.
Achieved whenan operator or inspection body publishes a side-by-side trial against certified inspectors on a stated number of items, with the share of faults missed and falsely flagged.
Claimed by
Mantl-Ex, in an article in Oilfield Technology, December 2025
Open
01
Score Ex photo readers
A labeled set of photos of Ex equipment, nameplates and installed details such as cable glands, covers and earthing, each with the correct reading of its Ex marking (protection type, gas group, temperature class, equipment protection level) and the faults a visual inspection would record, plus a score sheet that any app or AI model can be run against.
The briefCredit · unclaimed02
Compare zone calculators
A public comparison of how far hazardous zones reach around the same set of gas leaks, worked out by hand with the IEC 60079-10-1 method, with free online calculators and with an open gas dispersion model, and the spread between them reported.
The briefCredit · unclaimed
Open 01 · the brief
Score Ex photo readers
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A labeled set of photos of Ex equipment, nameplates and installed details such as cable glands, covers and earthing, each with the correct reading of its Ex marking (protection type, gas group, temperature class, equipment protection level) and the faults a visual inspection would record, plus a score sheet that any app or AI model can be run against.
Why it is still open
Mantl-Ex claims its model reads Ex markings and flags faults but has published no accuracy test. The public nameplate datasets found on Hugging Face hold a few dozen general nameplate images with no Ex markings, and searches found no labeled Ex marking set.
Built with what exists
Phone cameras; de-energized equipment photographed outside any hazardous area, in showrooms, training rigs or surplus stock; vision-language models that read text in photos, such as Claude, Gemini and GPT; a public table of gas groups and temperature classes by substance; a labeling tool such as Label Studio.
First step
Photograph and transcribe the nameplates of 50 pieces of Ex equipment at a supplier's showroom or a training center, with nothing powered.
Done looks like
500 photos labeled by two inspectors holding the IECEx Ex 007 unit, with their agreement rate, and published scores for at least three models: the share of markings read exactly and the share of mismatches with a stated zone and gas found.
Open 02 · the brief
Compare zone calculators
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A public comparison of how far hazardous zones reach around the same set of gas leaks, worked out by hand with the IEC 60079-10-1 method, with free online calculators and with an open gas dispersion model, and the spread between them reported.
Why it is still open
Choi and Byeon of Korea University noted in 2021 that edition 2.0 of IEC 60079-10-1, the international standard for classifying gas areas, gives its ventilation charts without equations, so each user or tool has to fit its own; free web calculators exist, such as Design Calculators' Zone Classification Helper, without published validation, and no side-by-side comparison was found.
Built with what exists
Python; OpenFOAM, an open fluid-flow simulator, or a simpler open dispersion model; release cases from published papers; a coding model such as Claude to write and cross-check the calculations.
First step
Take ten hydrogen and natural gas leak cases from published papers and run them through a hand calculation and one free calculator.
Done looks like
30 leak cases (gas, pressure, hole size, ventilation), each with zone type and extent from at least three methods, the spread published, and all inputs and code public.