This work fires a boiler and keeps it safe while it runs: the burner that mixes fuel and air, the flame detector that shuts the fuel off if the flame goes out, and the controls that stop the burner when the water runs low.
5
Milestones achieved, from About 1833 to 2026.
2
To watch for: announced, not yet confirmed outside.
3
Open deliverables. Nobody has shipped them.
The road
AchievedWatch forOpen
Achieved
About 1833
A whistle for low water
Edward A. Fagen writes in the National Board Bulletin that the steam whistle "was invented as a low-water alarm around 1833" by an itinerant Cornish mechanic, Adrian Stephens, who did not patent it. The first US patent for such an alarm went to Matthias Baldwin in 1846, and false alarms fell when a float through the top of the boiler worked the whistle.
LessonThe first water level control only warned a person, who still had to act.
Credit
Adrian Stephens; Matthias Baldwin
1930s
Burners that stop themselves
A low-water cutoff shuts off the burner when the water in a boiler falls too low. McDonnell & Miller, formed in 1924 by Everett Nicholas McDonnell with Pat Miller, says the automatic burners of the mid-1930s needed such a device, which led to its low-water cutoffs, and that by the end of the 1930s code authorities required pressure boilers to have one. Fireye says that in the 1930s it offered the first commercial electronic flame safeguard, a photoelectric device that sensed an oil flame "in less than a second" so that fuel could be cut off when the flame went out. Both accounts are the companies' own.
Credit
E. N. McDonnell and Pat Miller, McDonnell & Miller; Fireye
1999
Low water still kills
By the National Board's 1999 Incident Report, as reported by Power Engineering, accidents with boilers and pressure vessels in the US and Canada rose from 2,011 to 2,163 and deaths from 9 to 21, with low water one of the two leading causes in both years and burner failures and limit controls behind the most serious accidents. Ian D. Oldfield of Gestra wrote that floats stick with scale, probes are bridged by scale and circuits are jumpered or bypassed.
LessonFitting a safety control is not enough if it can be scaled up or bypassed without anyone knowing.
Credit
National Board of Boiler and Pressure Vessel Inspectors, which collected the reports
2018
Burners at 5 ppm
Nitrogen oxides (NOx) form when air is heated in a flame and help make smog. The South Coast Air Quality Management District in southern California, whose Rule 1146 for industrial boilers of 5 million Btu an hour and above dates from 1988, set a limit of 5 parts per million of NOx (at 3% oxygen, dry) for most gas-fired units from 7 December 2018, 7 ppm for many fire-tube boilers and 12 ppm for thermal fluid heaters.
Credit
South Coast Air Quality Management District
2026
Zero emissions for small boilers
The same district's Rule 1146.2, amended on 7 June 2024, sets a limit of 0 ppm of NOx and carbon monoxide for many gas-fired water heaters and small boilers of 2 million Btu an hour or less, which in practice means electric or other non-burning units. It applies to new buildings from 1 January 2026 and to existing buildings from 2029, with later phases to 2033.
Credit
South Coast Air Quality Management District
Watch for
A burner for any hydrogen share
Air Products says its boiler burner gives nearly identical steam output from 0 to 100% hydrogen blended with natural gas, with "low NOx", citing recent hydrogen boiler trials. It gave no NOx figure and did not say where the trials ran; Energies Media noted that no installation or outside test was mentioned.
Achieved whena named customer boiler runs on 100% hydrogen in regular service, with its NOx in ppm measured by a regulator or an independent tester.
Claimed by
Air Products, presented by Timothy Lebrecht, April 2026
Europe's largest electric boiler plant
An electrode boiler heats water by passing current through it, with no burner. The Helsinki energy company Helen says all four 50 MW electrode boilers at its Hanasaari plant, 200 MW in all, were installed by April 2026, for district heating in the 2026–27 heating season; FILTER supplied Zander & Ingeström units. Helen calls it the largest electric boiler plant in Europe.
Achieved whenHelen reports the plant in commercial operation at its full 200 MW.
Claimed by
Helen, April 2026
Open
01
A public record of boiler accidents
An open database of boiler and pressure vessel accidents from public records, each coded for cause, boiler type, the control involved, injuries and deaths, with a link to its source.
The briefCredit · unclaimed02
Flames labeled for flame-out
An open set of video frames of flames labeled stable, unstable or out, recorded alongside the signal of an ultraviolet sensor of the kind used in flame scanners, with a baseline model that tells the three apart.
The briefCredit · unclaimed03
Low-water probes under scale
A bench test, in an open tank of water at room temperature, of how scale coatings, bridging deposits and wiring faults make commercial low-water probes report water that is not there, with every trial logged.
The briefCredit · unclaimed
Open 01 · the brief
A public record of boiler accidents
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
An open database of boiler and pressure vessel accidents from public records, each coded for cause, boiler type, the control involved, injuries and deaths, with a link to its source.
Why it is still open
In the Summer 2005 Bulletin, National Board Executive Director Donald E. Tanner wrote that the Board had "decided to discontinue annual publication of the Incident Report" and focus on violation tracking. A search in November 2026 found no public, coded accident database that took its place.
Built with what exists
The National Board Bulletin archive; state boiler accident reports and news reports; the cause categories of the National Board's accident report form as a starting codebook; SQLite; an AI model to draft codes from each report, every code checked by a person.
First step
Copy the 1990s cause tables from the Bulletin archive into a spreadsheet and draft the codebook from them.
Done looks like
At least 200 accidents coded separately by two people, with their agreement (Cohen's kappa) of at least 0.7, published under an open license.
Open 02 · the brief
Flames labeled for flame-out
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
An open set of video frames of flames labeled stable, unstable or out, recorded alongside the signal of an ultraviolet sensor of the kind used in flame scanners, with a baseline model that tells the three apart.
Why it is still open
The closest public data set, from Landgraf and colleagues at the Karlsruhe Institute of Technology (2023), outlines industrial burner flames for segmentation but carries no labels for stability or flame-out.
Built with what exists
The KIT images; a small laboratory burner run under supervision in a university combustion lab, never a boiler; a camera; a UV photodiode and a data logger; CVAT for labels; PyTorch.
First step
Write the label rules and apply them to 500 frames from the KIT set to see whether stability can be judged from still images at all.
Done looks like
At least 10,000 labeled frames with the sensor signal, and a baseline model's recall on the "out" class reported on held-out recordings.
Open 03 · the brief
Low-water probes under scale
The first to publish is credited on this line, and the deliverable moves from Open to Achieved.
What to build
A bench test, in an open tank of water at room temperature, of how scale coatings, bridging deposits and wiring faults make commercial low-water probes report water that is not there, with every trial logged.
Why it is still open
Oldfield's 1999 Bulletin article lists these failure modes but gives no measurements, and a search in November 2026 found no published table of how often each fault defeats a probe.
Built with what exists
Commercial conductance probes and controllers; water mixed to set conductivities; coatings that mimic scale; a data logger.
First step
Turn Oldfield's list into a test matrix and buy two probes and controllers from different makers.
Done looks like
A published table of trip and false "water present" rates for each fault and each probe, from at least 30 trials per condition.